We repair and service Himoinsa generator sets on site across Gauteng, whichever engine and alternator the set carries. Himoinsa, a Spanish builder, assembles complete sets around engines from makers such as Yanmar, Kubota, FPT (Iveco), Doosan, Scania and Volvo, so the first step on any job is to identify the engine from its own plate before ordering filters or parts.

  • Established 2006

    20 years of experience

  • 24/7 operations

  • We Arrive Within 1–2 Hours

    (usually within 1 hour)

  • Free callouts and quotations

  • One-year warranty

  • Qualified and certified technicians

  • We Service & Repair All Generator Brands

    All generator makes and models

  • 1 kVA–20,000 kVA capability

Four places that tell us what is inside

A Himoinsa set is assembled from parts made by different companies, so its specifications come from several sources. Before quoting, we read the engine data plate, the alternator plate, the front of the controller and the set’s own nameplate on the canopy or base frame. The diagram shows where each one sits on a typical canopied set of any make.
Cut-away diagram of a canopied generator set. Main parts: 1 radiator and fan, 2 air filter, 3 engine, 4 alternator, 5 terminal box and AVR, 6 controller, 7 starting battery, 8 exhaust silencer, 9 base fuel tank. Where the names are: A engine data plate on the block or rocker cover, B alternator plate on its housing, C the controller front, D the set nameplate on the canopy or base frame.
Where the engine, alternator, controller and set plates are found on a typical canopied generatorOpen full size (opens in a new tab)

Who made which part of a Himoinsa set

Who made which part of a Himoinsa set
PartUsually made byWhat it decides
EngineUsually made byYanmar or Kubota on smaller sets; FPT (Iveco), Doosan, Scania, Volvo and others on larger onesWhat it decidesOil grade, filters, service schedule and the engine’s protection senders
AlternatorUsually made byMecc Alte or another specialist makerWhat it decidesAVR type, excitation, bearings and winding repairs
ControllerUsually made byHimoinsaWhat it decidesStart mode, protection limits, timers and mains sensing
Canopy, base frame and tankUsually made byHimoinsaWhat it decidesFuel capacity, spill containment, sound insulation and air paths

On many models the letters before the size hint at the engine, as with HYW sets and their Yanmar engines, but sets with similar names from different years can still differ. The data plate settles it.

Which Himoinsa panel does your set have?

Himoinsa fits its own controllers, such as the CEM7 for manual or remote starting and the CEA7 for automatic mains-failure operation, found on many sets. The panel type decides how the set behaves when the power goes off, and that is often the first thing to establish when a Himoinsa set did not come on.
Which Himoinsa panel does your set have?
Panel typeHow it worksWhere faults usually are
ManualHow it worksStarted and stopped by an operator at the panelWhere faults usually areStart circuit, emergency stop, protection shutdowns
Automatic startHow it worksStarts on a remote signal, such as a separate mains monitor or a building systemWhere faults usually areRemote start wiring, controller mode, battery
Automatic with changeoverHow it worksWatches the mains, starts the set and transfers the loadWhere faults usually areMains sensing, contactors or motorised switch, timers

When a Himoinsa set did not come on

During load shedding a standby set is expected to start without anyone touching it. When it does not, we work from the controls towards the engine.
  1. 01

    Panel mode and emergency stop

    An automatic panel left in manual or off, or a set stopped with the emergency stop, will not start on mains failure.

  2. 02

    Alarm history

    The controller logs what stopped the set. A low oil pressure or high temperature shutdown points somewhere very different from a failed start.

  3. 03

    Battery and charger

    A set on standby depends on its battery charger, and a weak battery is one of the commonest reasons a set will not crank.

  4. 04

    Start signal and changeover

    On automatic sets, faulty mains sensing or changeover wiring leaves a healthy set waiting for a signal that never comes.

  5. 05

    Fuel, air and engine

    Only once the controls and power supply are proved do we move to the fuel system and engine, using the engine maker’s figures.

Service points

Looking after a Himoinsa set

Servicing by duty, not by name

A Himoinsa set on prime power at a site is serviced by running hours; a standby set at a building is serviced by time as well, because it may only run a few hours between services. Both follow the schedule of the engine fitted, which is why two Himoinsa sets of the same size can need different filters and intervals.

Routine servicing covers the engine, cooling, fuel, battery and controller, and a maintenance plan keeps those visits on schedule. For a breakdown, our generator repairs team comes to the set.

Independent service

We Service & Repair All Generator Brands

Onsite Generator Repairs is an independent generator specialist. We repair, service and maintain Himoinsa equipment as part of our work on every make of generator.

Manufacturer warranty claims go through the manufacturer’s own network. If your generator is still under warranty, check the warranty terms before arranging work by anyone else.

Brand names and trademarks belong to their respective owners. Onsite Generator Repairs is an independent service and repair company.

Service areas

Where we work in Gauteng

We come to you, wherever the Himoinsa equipment is installed: on-site repairs, servicing and maintenance in all five Gauteng regions.

FAQ

Frequently asked questions

How do I know which engine my Himoinsa generator has?

Check the data plate on the engine itself, or the set’s documentation. A photo of the plate is enough for us to identify it.

Is Himoinsa connected to Yanmar?

Himoinsa is part of the Yanmar group, and many smaller Himoinsa sets carry Yanmar engines. Larger sets use engines from other makers, so check the plate.

Can an automatic changeover be added to a manual Himoinsa set?

Usually, with a suitable controller and changeover panel. It is electrical installation work that must comply with the wiring regulations; see generator installation.

Are parts available for Himoinsa generators?

Engine and alternator spares are usually the easiest, because those makers’ parts are widely stocked. Controller boards, canopy panels and tank parts are specific to Himoinsa, so we look them up from the set’s nameplate and give you a realistic lead time with the quote.

Need a generator technician?

  • 24/7 operations
  • We Arrive Within 1–2 Hours (usually within 1 hour)
  • Free callouts and quotations
Call nowWhatsApp us