Why a Generator Surges, Hunts or Drifts Off 50 Hz

The short answer

A generator surges or hunts when its governor cannot hold the engine at a steady speed, and because the output frequency comes straight from engine speed, the 50 Hz supply swings with it. The usual causes are fuel starvation or air in the fuel, a worn or badly set governor, a sticking actuator or linkage, or a load that is too large or very light. Left alone it upsets clocks, motors and UPS units, and it usually gets worse.

  • Read the frequency (Hz) on the controller or meter
  • Note whether it hunts with no load, or only under load
  • A recent run-dry or filter change often means air in the fuel
  • Inverter generators change engine speed by design
Green diesel engine inside a generator canopy, with its fuel filter, injection pump and pipework

Need it fixed rather than diagnosed?

Free callouts and quotations. We arrive within 1–2 hours, usually within 1 hour.

Surging, hunting or sagging: reading the pattern

Listen to the engine and watch the frequency reading at the same time. The pattern narrows the cause quickly.
Surging, hunting or sagging: reading the pattern
SymptomLikely causesRepair route
Rhythmic rise and fall with little or no load (hunting)Likely causesGovernor gain or droop set wrongly, worn or sticking linkage, a sticking actuator, or very light load on a mechanically governed engineRepair routeGovernor set-up and linkage repair
Surges after running dry, refuelling or a filter changeLikely causesAir in the fuel from a system that was not bled properly or a loose suction-side fitting, or a weak lift pumpRepair routeFuel system repairs
Random surges that get worse as the tank runs lowLikely causesPickup drawing air or sludge, a blocked tank vent, water or diesel bug in the fuelRepair routeFuel contamination checks
Speed drops sharply when load comes onLikely causesOverload, a partly blocked fuel filter or water separator, slow governor response, worn injection components, a blocked air filterRepair routeLoad, fuel and air checks
Steady, but slightly slower under loadLikely causesNormal droop on a mechanically governed engine, if it stays within limitsRepair routeOften normal
Small petrol unit surges at no loadLikely causesCarburettor jet partly blocked by stale fuel, an air leak at the intake, a sticking governor spring or linkageRepair routePetrol generator repair
Engine races, then an overspeed shutdownLikely causesSticking fuel rack or actuator, a governor fault, or a false trip from a faulty speed signalRepair routeShutdowns and trips
UPS or battery inverter rejects generator powerLikely causesFrequency or voltage moving outside the range the equipment accepts, or a distorted waveform from a small setRepair routeSpeed and voltage checks

How it works

Speed is frequency: why 50 Hz depends on the engine

A conventional generator’s alternator is turned directly by the engine, so the output frequency is set by engine speed and the number of poles. For 50 Hz, a four-pole alternator must turn at 1,500 rpm, which suits most standby diesels; many small petrol and air-cooled units use a two-pole alternator at 3,000 rpm. Any change in speed is a change in frequency, which is why surging shows up on the hertz reading before anything else.

Mechanical governors are set with a little droop: the speed sits a few percent high with no load and falls towards 50 Hz as load rises. Electronic governors and engine control units can hold the speed constant at any load (isochronous control). Inverter generators work differently again: the engine speeds up and slows down with the load, and the electronics produce a steady 50 Hz regardless. Our guide to voltage and frequency basics explains the relationship in more detail.

  • Hz = rpm × poles ÷ 120
  • 1,500 rpm for 50 Hz on a four-pole set
  • Droop is normal; hunting is not
Frequency in hertz equals engine speed in rpm times the number of poles divided by 120. A four-pole alternator at 1,500 rpm gives 50 Hz; a two-pole alternator at 3,000 rpm gives 50 Hz. A chart shows a droop governor letting frequency fall slightly as load rises, while isochronous control holds it steady at 50 Hz. Inverter generators make 50 Hz electronically.
Engine speed sets the frequencyOpen full size (opens in a new tab)

Mechanical, electronic and inverter speed control

The kind of speed control your generator has decides what can go wrong with it.
Mechanical, electronic and inverter speed control
Speed controlHow it holds speedWhere it goes wrong
Mechanical governorHow it holds speedFlyweights in the engine or injection pump move the fuel rack (or the throttle on a petrol engine) through a spring and linkageWhere it goes wrongWorn flyweights and pivots, a tired spring, sticking or loose linkage, wrong speed or droop setting
Electronic governorHow it holds speedA magnetic speed pickup reads the flywheel teeth, and a governor controller drives an actuator on the fuel pumpWhere it goes wrongDirty or badly gapped pickup, sticking actuator, loose wiring, gain or stability set wrongly
Engine control unitHow it holds speedThe engine’s own electronics read crank and cam sensors and meter the fuel electronicallyWhere it goes wrongSensor and wiring faults, low fuel pressure, configuration; the unit usually logs a fault
Inverter generatorHow it holds speedEngine speed follows the load; the inverter module makes 50 Hz electronicallyWhere it goes wrongAn unsteady engine at a constant load points to fuel or throttle control; wrong output frequency points to the inverter module

Causes explained

Where surging and hunting come from

  • Fuel starvation: Fuel system repairs

    A governor can only ask for more fuel; it cannot deliver fuel the system will not supply. Partly blocked filters, a clogged water separator, a weak lift pump or a restricted tank pickup starve the engine as demand rises, so it sags and recovers in surges.

  • Air in the fuel

    Running the tank dry, a filter change that was not bled properly, or a loose fitting on the suction side lets air in. Bubbles reaching the injection pump give random surges and can stall the engine.

  • Governor and linkage wear

    Free play in the linkage, worn flyweight pivots or a weak spring make the governor late to respond, so it overcorrects in both directions. That is the classic rhythmic hunt.

  • Actuator and speed pickup

    On electronically governed sets, a sticking actuator or a dirty, loose or badly gapped speed pickup gives erratic speed, overspeed trips or a shutdown for loss of speed signal.

  • Very light load

    With almost nothing connected, the governor works near its minimum fuel position, where linkage friction and small settings matter most. Long evening runs at light load during load shedding are a common trigger, and they also cause wet stacking.

  • Overload and big load steps: kVA sizing guide

    A load beyond the set’s rating, or several motors starting at once, pulls the speed down faster than the governor can recover. Black smoke with a falling frequency usually means overload.

Why the frequency matters in your building

Mains power in South Africa is 50 Hz, and a lot of equipment assumes it. Induction motors in pumps, compressors and fans run faster or slower with the frequency, and low frequency at full voltage makes motors and transformers run hot. Clocks on ovens, microwaves and some timers count the supply’s cycles, so they gain or lose time on a generator that runs off speed.

A frequent complaint during load shedding is a UPS or battery inverter that refuses the generator. Most UPS units, and the backup and hybrid inverters many homes now have, only accept input within a set window of frequency and voltage. A hunting generator drifts in and out of that window, so the UPS keeps switching to battery, runs it down and may drop the load. Some units have a sensitivity or generator setting, described in their manual or set by their installer, that widens the window. That can help with a healthy set’s normal droop, but it will not cure a generator that is genuinely hunting.

Checks you can make without opening anything up

  • The frequency at no load and again with load applied, from the controller or meter
  • Whether the surging is rhythmic (usually the governor) or random (usually fuel or electrical)
  • Whether it eases when you switch off large loads
  • The fuel level, and whether the set recently ran dry, was refuelled from containers or had a filter change
  • The air filter restriction indicator, if one is fitted, with the engine stopped
  • Any alarms on the controller, and the hour-meter reading

Tell us whether the set has been running long evening hours on light load. It changes where we look first.

Repair options for a surging engine

We measure speed across the load range, then check fuel and air before touching the governor, because no governor setting can fix a fuel problem. Many surging engines need fuel system repairs rather than governor work.
Repair options for a surging engine
Cause foundWhat the repair involves
Fuel restriction or air leakWhat the repair involvesReplace filters, drain the water separator, find and fix the leak, bleed the system and test lift pump delivery
Contaminated fuelWhat the repair involvesDrain water and sludge, arrange cleaning or replacement of the fuel, and change the filters
Governor out of adjustmentWhat the repair involvesSet speed, droop and gain so the engine holds steady from no load to full load
Worn linkage or mechanical governorWhat the repair involvesRepair or replace the worn parts, then set the governor up again
Sticking actuator or faulty speed pickupWhat the repair involvesClean, re-gap or replace, and check the wiring and governor controller
Carburettor fault (petrol units)What the repair involvesClean or replace the carburettor and refill with fresh fuel
Overload or large load stepsWhat the repair involvesStagger motor starts, move loads, or size a larger set
Long runs at very light loadWhat the repair involvesPlan load during long runs and test under load; a load bank test can be arranged

FAQ

Frequently asked questions

Why is my generator surging?

Most often because the engine is not getting a steady supply of clean fuel: a blocked filter, air in the lines or a weak lift pump. A worn or badly set governor, a sticking actuator and very light or very heavy loads are the other common causes. Rhythmic surging points to the governor; random surging points to fuel.

Why does my UPS switch to battery when the generator is running?

Most UPS units only accept input within a set range of voltage and frequency. A generator whose speed hunts, or whose voltage swings, falls outside that range and the UPS rejects it. Stabilising the generator usually solves it, although some small sets produce a waveform that sensitive units reject even at a steady speed.

Is it normal for the engine to slow slightly under load?

On mechanically governed engines, a small drop is normal and designed in. A large drop, or one that keeps getting worse, is not.

What frequency should a generator run at?

50 Hz in South Africa. A four-pole set needs 1,500 rpm for that and a two-pole set 3,000 rpm. Mechanically governed sets run slightly above 50 Hz with no load and settle close to 50 Hz at full load.

Why does my inverter generator speed up and slow down?

Most inverter generators have an economy mode that runs the engine only as fast as the load needs. The output frequency stays at 50 Hz because the inverter produces it electronically.

Can surging damage the generator?

It can. A hunting engine wears the governor and linkage, the AVR works harder to follow the changing speed, and running short of fuel or on air can damage an injection pump that relies on diesel for lubrication. Connected motors and electronics suffer too.